メニュー起動コマンド
$ sudo apctest
※Apcupsd が動作中の場合は、このコマンドを実行する前に、stop しておくこと
※表示例は抜粋
メインメニュー
1) Query the UPS for all known values
2) Perform a Battery Runtime Calibration
3) Abort Battery Calibration
4) Monitor Battery Calibration progress
5) Program EEPROM
6) Enter TTY mode communicating with UPS
Q) Quit
スポンサードリンク
1) Query the UPS for all known values
UPS に関する既知の値を表示(たぶん)
UPS Status: 0C Line quality: FF Reason for last transfer to batteries: O Self-Test Status: NO Line Voltage: 089.2 Line Voltage Max: 091.4 Line Voltage Min: 089.2 Output Voltage: 100.0 Batt level percent: 100.0 Batt voltage: 27.27 UPS Load: 033.1 Line freq: 50.00 Runtime left: 0037 UPS Internal temp: 031.9 Dip switch settings: NA Register 1: 00 Register 2: 00 Register 3: 00 Sensitivity: M Wakeup delay: 000 Sleep delay: 180 Low transfer voltage: 092 High transfer voltage: 108 Batt charge for return: 90 Alarm status: 0 Low battery shutdown level: 02 UPS Name: UPS_IDEN UPS Self test interval: 168 UPS manufacture date: 08/26/05 UPS serial number: ********** Date battery replaced: 08/26/05 Output voltage when on batteries: 100 Nominal battery voltage: 024 Percent humidity: NA Ambient temperature: NA Firmware revision: 601.12.A Number of external batteries installed: 000 Number of bad batteries installed: NA UPS model as defined by UPS: FWA UPS EPROM capabilities string: u360420E443336168ON OFF The EPROM string is 286 characters long! Hours since last self test: NA
2) Perform a Battery Runtime Calibration
これを実行すると、UPS がワザと停電状態にするようで、バッテリのチェックを行えるようだ。
Checking estimated runtime ... Current runtime is 37 minutes Checking for battery level ... Battery level is 100.0 -- OK The battery calibration should automatically end when the battery level drops below about 25, depending on your UPS. I can also optionally monitor the progress and stop the calibration if it goes below 10. However, in the case of a new battery this may prematurely end the calibration loosing the effect. Do you want me to stop the calibration if the battery level goes too low? (y/n): Sending Battery Calibration command. ... UPS has initiated battery calibration. Monitoring the calibration progress ... To stop the calibration, enter a return. Battery charge 87 Remaining runtime is 32 minutes ..... Battery charge 77 Remaining runtime is 29 minutes User input. Terminating calibration ... Attempting to abort calibration ... Response to abort request: OK On battery 84 sec or 1m24s.
4) Monitor Battery Calibration progress
バッテリ駆動が可能な時間を表示してくれるようだ。
Monitoring the calibration progress ... To stop the calibration, enter a return. Battery Runtime Calibration terminated by UPS. Checking estimated runtime ... Remaining runtime is 29 minutes
5) Program EEPROM
UPS に内蔵されているEPROM に関する操作ができるようだ。
This is the EEPROM programming section of apctest. Please select the function you want to perform. 1 ) Print EEPROM values 2 ) Change Battery date 3 ) Change UPS name 4 ) Change sensitivity 5 ) Change alarm delay 6 ) Change low battery warning delay 7 ) Change wakeup delay 8 ) Change shutdown delay 9 ) Change low transfer voltage 10 ) Change high transfer voltage 11 ) Change battery return threshold percent 12 ) Change output voltage when on batteries 13 ) Change the self test interval 14 ) Set EEPROM with conf file values Q ) Quit
1) Print EEPROM values
EPROM に現在設定されいている値と、設定可能な値が表示されるようだ。
Doing prep_device() ... Valid EEPROM values for the Smart-UPS 1500 Config Current Permitted Description Directive Value Values =================================================================== Upper transfer voltage HITRANSFER 108 108 110 112 114 Lower transfer voltage LOTRANSFER 92 092 090 088 086 Return threshold RETURNCHARGE 90 00 15 30 45 60 75 90 Output voltage on batts OUTPUTVOLTS 100 100 Sensitivity SENSITIVITY M H M L Low battery warning LOWBATT 2 02 05 08 11 14 17 20 23 Shutdown grace delay SLEEP 180 090 180 270 360 450 540 630 000 Alarm delay BEEPSTATE 0 0 T N Wakeup delay WAKEUP 0 000 060 120 180 240 300 360 420 Self test interval SELFTEST 168 336 168 ON OFF =================================================================== Battery date: 08/26/05 UPS Name : UPS_IDEN
11) Change battery return threshold percent
復電した際にUPS が復帰するために必要な充電量を変更するようだ。この例では 90% 充電されないと復帰されないのを 15% 充電したら復帰するように変更した。
Enter new battery return level: 15 The old UPS return threshold percent is: 90 The new UPS return threshold percent is: 15
コメント